The fault phenomenon |
The cause of the problem |
Troubleshooting and solutions |
Short battery discharge time |
Cell aging |
Replace the battery in time |
UPS overload |
Check load levels and remove unimportant loads |
|
1#The fault indicator light and no. 6 light are on, and the buzzer is ringing |
The fault indicator light and no. 6 light are on, and the buzzer is ringing |
Make sure the UPS are not overloaded, the vents are not blocked, and the indoor temperature is not too high. Let the UPS cool for 10 minutes, then restart. If it fails, please contact us at 010-86524278 |
1#The fault indicator light and no. 5 light are on and the buzzer is ringing |
UPS output short circuit or UPS shutdown due to internal fault |
Turn off the UPS, remove all loads, and make sure there is no fault or internal short circuit in the load. Restart. If it fails, please contact the vendor or manufacturer. |
1#The failure indicator light and no. 4 light are on, the UPS is ringing |
UPS shut down due to internal failure |
Please contact the vendor or manufacturer. |
1#The failure indicator light and no. 3 light are on, the UPS is ringing |
UPS overcharge protection action |
UPS charger failure,
Please contact the vendor or manufacturer.
|
The power indicator is flashing |
The mains voltage or frequency is beyond the input range of UPS (UPS calls twice a second and eight times continuously when starting up) |
At this point UPS is working in battery mode, saving the data and closing the application, ensuring that the mains is within the input voltage or frequency range allowed by UPS |
Mains power zero, fire wire connection is reversed, UPS two minutes one call |
Reconnect so that the power line is properly connected |
|
1#The failure indicator light and no. 2 lamp are on, the UPS is ringing |
Battery mode UPS overload or load equipment failure |
Check the load level and remove non-critical equipment, recalculate the load power and reduce the amount of load connected to the UPS to check the load equipment for failure |
Battery lamp flashing |
Battery voltage is too low or the battery is not connected |
Check the part of UPS battery and connect the battery. If the battery is damaged, replace the battery as soon as possible |
1#The fault light is on, the battery light is flashing, and the buzzer beeps every second |
UPS charging part is out of order |
Please contact the vendor or manufacturer. |
Normal power supply, UPS does not enter the market |
UPS input circuit breaker open |
Reset the circuit breaker manually |
Short battery discharge time |
Battery undercharging |
Keep UPS connected to the mains power for more than three hours to recharge the battery |
UPS overload |
Keep UPS connected to the mains power for more than three hours to recharge the battery |
|
Batteries age and capacity declines |
To replace the battery, please contact the dealer for the battery and its components |
|
After the power button is pressed, UPS cannot start |
Pressing the power button is too short |
Press the power button for more than one second to start UPS |
UPS does not connect the battery or the battery is low and loaded to boot |
Connect the UPS battery. If the battery is low, turn off the power first and start up again |
|
UPS internal failure |
Please contact the vendor or manufacturer. |